FROH2R |
printable (italian only) version
 versione italiana  english version
Flame retardant cables, reduced emission of corrosive gasses
Multicore flexible cable copper braid screening, flame retardant, reduced emission of corrosive gasses
CEI 20-20, CEI 20-22 II, CEI 20-52
 |
 |
 |
 |
cores colour
|
Blu,Marrone-Giallo/Verde,Blu,Marrone-Marrone,Nero,Grigio-Giallo/Verde,Marrone,Nero,Grigio-Blu,Marrone,Nero,Grigio |
 |  |  |
 |
sheaths colour |
Grey RAL 7035 |
 |  |  |
 |
marking |
Progressive metric - Mondini Cavi - CEI 20-22 II - FROH2R 450/750 V - form. x sect. - ECO - CE - Production Year |
 |  |  |
 |
insulating |
PVC TI2 |
 |  |  |
 |
sheath |
PVC Antiabrasive TM2 |
 |  |  |
 |
rated voltage |
450/750 V |
 |  |  |
 |
test voltage |
2500 V C.A. |
 |  |  |
 |
bending radius |
6 times outer diameter of cable for mobile service - 4 times outer diameter of cable for fixed lay |
 |  |  |
 |
tensile stress |
15 N per mmq. di sezione del rame |
 |  |  |
 |
max working temperature |
70° C |
 |  |  |
 |
max short circuit temperature |
160° C |
 |  |  |
 |
minimum layng temperature |
0° C |
 |  |  |
 |
use |
Internally in dry or damp premises, externally for intermittent or temporary use. Suitable for fixed installation and for connection fixed or moving appliances. For signalling, switching, measuring and regulation installations where the use of the screen is indispensable for eliminating disturbances induced by external electromagnetic fields. Excellent flexibility also at low temperature. |
N° of conductors for rated cross section |
 |
Max Ø of conductor strands |
 |
Insulation thickness |
 |
Sheath thickness |
 |
Finished cable Ø |
 |
Approx. weight |
 |
Electrical resistance at 20° C |
 |
Mutual capacity |
 |
|
 |
|
 |
|
2 x 1 |
 |
0,21 |
 |
0,6 |
 |
0,8 |
 |
7,4 |
 |
83 |
 |
19,5 |
 |
140 |
 |
|
 |
|
 |
|
3 x 1 |
 |
0,21 |
 |
0,6 |
 |
0,8 |
 |
7,8 |
 |
97 |
 |
19,5 |
 |
140 |
 |
|
 |
|
 |
|
4 x 1 |
 |
0,21 |
 |
0,6 |
 |
0,9 |
 |
8,6 |
 |
119 |
 |
19,5 |
 |
140 |
 |
|
 |
|
 |
|
2 x 1,5 |
 |
0,26 |
 |
0,7 |
 |
0,9 |
 |
8,4 |
 |
110 |
 |
13,3 |
 |
150 |
 |
|
 |
|
 |
|
3 x 1,5 |
 |
0,26 |
 |
0,7 |
 |
0,9 |
 |
8,8 |
 |
128 |
 |
13,3 |
 |
150 |
 |
|
 |
|
 |
|
4 x 1,5 |
 |
0,26 |
 |
0,7 |
 |
1,0 |
 |
9,8 |
 |
161 |
 |
13,3 |
 |
150 |
 |
|
 |
|
 |
|
2 x 2,5 |
 |
0,26 |
 |
0,8 |
 |
1,1 |
 |
9,2 |
 |
168 |
 |
7,98 |
 |
150 |
 |
|
 |
|
 |
|
3 x 2,5 |
 |
0,26 |
 |
0,8 |
 |
1,1 |
 |
10,7 |
 |
194 |
 |
7,98 |
 |
150 |
 |
|
 |
|
 |
|
4 x 2,5 |
 |
0,26 |
 |
0,8 |
 |
1,1 |
 |
11,7 |
 |
238 |
 |
7,98 |
 |
150 |
 |
|
 |
|
 |
|
back to:Flame retardant cables, reduced emission of corrosive gasses
back to catalouge
home | news | company overview | productive cycle | catalogue | contacts
|
|