torna alla home archivio news azienda ciclo produttivo catalogo prodotto come contattarci accedi all'area privata
 





YSLY-CY

 

printable (italian only) version

versione italiana english version

Other types of cables
Multicore flexible cable, tinned copper screening, transparent outer sheath
Conductor identification according to VDE 0293 - PVC flame retardant

cores colour

sheaths colour

Tansparent,Grey RAL 7001

marking

On customer request

insulating

PVC TI2

sheath

PVC TM2

rated voltage

600/1000 V

test voltage

4000 V C.A.

bending radius

15 times outer diameter of cable

tensile stress

15 N per mmq. di sezione del rame

max working temperature

Installazione mobile da -5° C a +80° C - Installazione fissa da -30° C a + 80° C

max short circuit temperature

minimum layng temperature

use

For power supply to electrical equipments, components and machines. Indoor installation in dry or damp conditions, for fixed and moving laying. For signal transmission in machines, computer system or electronic equipement. The high covering percentage of the copper assures disturbance free transmission of all signals and data.


N° of conductors for rated cross section

Max Ø of conductor strands

Insulation thickness

Sheath thickness

Finished cable Ø

Approx. weight

Electrical resistance at 20° C



back to:Other types of cables